TO USE THESE SPECS, SIMPLY CHECK OR WRITE IN THE APPLICABLE DETAILS IN EACH SECTION
1.
Sectional walk-in refrigerators
and/or freezers complete with doors shall be manufactured by Bally Refrigerated
Boxes, Inc., and supplied by BMIL International, Inc. Overall size of walk-in
shall be _____long x _____wide x _____high. Fill in lengths and widths from this
list: 5'10", 6'9-1/2", 7'9", 8'8-1/2", 9-8",
10-7-1/2", 11-7", 12'6-1/2", 13'6", 14'5-1/2",
15-5", 16-4-1/2", 17'4", 18'3-1/2", 19'3",
20'2-1/2", 21'2", 22'1-1/2", 23'1", 24'1/2",
25'0", 25'11-1/2", 26'11 ", 27'10-1/2". Longer or wider
buildings are available in additional 11-1/2" increments.
Fill in heights from this list (heights shown are with floor; subtract 4" for less-floor units): 7'6", 8'6", 9'6", 10'6", 12', 13', 14', 15', 16', 17', 18', 19', 20'4", 21-4", 22-4", 23'4", 24'4", 25-4", 26-4", 27-4", 28'4". (Single length verticals)
Taller buildings are available in additional 12" increments, with stacked vertical panels.
2.
Foam core of panels shall be
Underwriters Laboratories-listed as having flame spread of 25 or lower and smoke
generation of 450 or lower when tested in accordance with ASTME-84-76. Panels
shall be approved by FM (Factory Mutual) as a Class I building type. They shall be
foamed using
enovate�
3000 Zero Ozone Depletion
Potential (0 ODP) expanding agent and shall meet all current international
standards.
3.
All work and materials shall be in full accordance with local and/or state
ordinances, and with any other prevailing rules and regulations.
Bally Refrigerated Boxes, Inc./BMIL International, Inc., is not responsible for
furnishing items required by the regulations, unless specified or shown on the
drawings or contained in the specifications.
4.
Panels shall consist of interior and exterior metal skins precisely formed
with steel dies and roll-form equipment and thoroughly checked with gauges for
accuracy. The metal skins shall be placed into heated molds and liquid urethane
injected between them. For extra rigidity, the exteriors of all vertical panels
except corners and door panels shall have vertical grooves spaced on 5-3/4"
centers. Urethane shall be foamed-in-place (poured, not frothed) and, when
completely heat-cured, shall bind tenaciously to the metal skins to form an
insulated panel. Panels shall contain 100 percent urethane insulation and have
no internal wood or structural members between the skins. To insure tight
joints, panel edges must have foamed-in-place tongues and grooves with a
flexible vinyl gasket on the interior and exterior of all tongue edges. Gaskets
shall be resistant to damage from oil, fats, water and detergents and must be
NSF-approved. Panel thickness: 4"___- 5"___- 6"___.
5. Exterior Finish
A. ___ Stucco-embossed Galvalume steel
B. ___ Smooth galvanized steel with white polyester painted finish
C. ___ Stainless steel
D.___ Stucco-embossed aluminum
E. ___ Stucco-embossed aluminum with white polyester painted finish
F. ___ Stucco-embossed galvanized steel with sand-tan polyester painted finish
G. ___ Stucco-embossed galvanized steel with white polyester painted finish
H. ___ Kynar over steel
I. ___ Sandex stone-textured finish over steel
6. Interior Finish
A. ___ Stucco-embossed Galvalume steel
B. ___ Smooth galvanized steel with white polyester painted finish
C. ___ Stainless steel
D. ___ Stucco-embossed aluminum
E. ___ Stucco-embossed aluminum with white polyester painted finish
F. ___ Stucco-embossed galvanized steel with sand-tan polyester painted finish
G. ___ Stucco-embossed galvanized steel with white polyester painted finish
7.
All panels except corner panels shall be made in 23" and 46" widths,
fully interchangeable for fast, easy assembly. Panels 11-1/2", 17-1/4"
or 34-1/2" wide are to be furnished only if required to fit the allocated
space. To assure perfect alignment and maximum strength, corner panels shall
employ a right-angle configuration with exterior horizontal dimensions of
12" on each side. Vertical panels (except corner panels) shall be supplied
in a single length up to 28' high (16' high for installations with aluminum or
stainless steel finish). For outdoor applications, single-height panels greater
than 19' (16' for aluminum) or multi-tiered vertical panels must be secured to
horizontal girts mounted between building columns.
8.
Panels shall be equipped with Bally Speed-lok diaphragmatic joining devices. The
distance between locks shall not exceed 46". Each device shall consist of a
cam-action, hooked locking arm placed in one panel, and a steel rod positioned
in the adjoining panel, so that when the arm is rotated, the hook engages the
rod and draws the panels tightly together with cam action. Arms and rods shall
be housed in individual steel pockets. Pockets on one side of the panel shall be
connected to pockets on the other side in width, by the use of 2"-wide
metal straps set into and completely surrounded by the insulation. When panels
are joined together, these straps shall form lock-to-lock connections for extra
strength.
9. Floor Construction -
Bally furnishes floor panels only. All construction and preparation for
Bally floor panels must be provided by others. Floor panel construction shall be
similar to that described in sections 7 and 8 above, but with a heavier-gauge
interior skin; thickness of floor panels may be different than that of vertical
panels. 4"-thick floor panels can be NSF or non-NSF. 5"- and
6"-thick panels are non-NSF.
A. ___ Light-usage Floor - Floor panels shall be placed on a concrete pad and leveled. Where inside floor and outside platform must be level, the concrete pad shall be made with a depression deep enough to receive the Bally floor panels.
B. ___ Heavy-usage Floor - Floor panels shall be placed on a depressed concrete pad and leveled. After supporting steel is assembled, a 4" reinforced concrete wearing floor shall be poured. The depression shall be deep enough to make interior and exterior finished floors the same height.
C. ___ Built-in, Insulated Floor - The floor shall be constructed on the job site. It shall consist of a depressed, reinforced concrete sub-slab. Slab urethane shall be built into this depressed slab and tile floor or 4" reinforced concrete wearing floor installed on top. Wall panels shall be fastened to this floor Adequate drainage and ventilation or other heat source must be provided beneath and around all construction.
Floor Panel Finishes
A. ___ 14 ga. galvanized steel
B. ___ 16 ga. stainless steel
Special Construction Floor Panels
A. ___ Reinforced Floor Panels - 4"-thick insulated floor panels
contain non-conductive structural imbeds for maximum strength without freezing.
Standard steel plate overlay adds strength. Panels support up to 1200 pounds per
square foot (evenly distributed) and support pallet jacks or light forklifts
with total weight of up to 2000 pounds per wheel (diamond plate overlay
required).
Hinged Entrance Door Panels
Number of doors ____
Width and height of each door
_____________________________
(Select dimensions from this list.-)
Widths: 30", 36", 42", 48", 60"
Heights: 78", 84"
Number of doors, location and direction of swing is specified on the plans. Doors are in-fitting and flush-mounted.
Construction shall be as specified in 7.
Magnetic core, thermoplastic gaskets installed on the top edge and both sides of the door shall keep the door in a closed position, forming a tight seal; a flexible, dual-blade wiper gasket shall be installed at the bottom of the door. NSF-approved gaskets shall be replaceable and resistant to damage from oil, fats, water and detergent.
A heavy U-channel structural steel frame around the perimeter of the door opening shall prevent racking or twisting; steel frame is to be reinforced for hardware attachment.
Anti-condensate heater wire shall be concealed behind the metal edge of the door jambs. The door panel shall also include a vapor-proof interior lamp; junction box for 120v., 60 cycle, 1 phase, a.c. service (15 amp maximum); 2"-dia. flush-face dial thermometer (field mounted on 60" wide doors); and weather hoods for outdoor installations.
Hardware
A. ____ For doors with 30" or 36"-wide openings: two
spring-loaded, self-closing hinges; cylinder latch with provision for padlocking
and safety release mechanism; door closer
B. ____ For doors with 42", 48" or 60"-wide openings: hinges are uplift type with blades not less than 9" long; latch shall include provision for padlocking and safety release mechanism.
Hardware Finishes
A. ____ For walk-ins finished with stainless steel polished aluminum
B. ____ For walk-ins with finishes other than stainless steel - satin aluminum
C. ____ For walk-ins with any finish (if desired) chrome-plated
Door Options
A. ____ Hinged Super Entrance Door
Construction is identical to that of a standard door except that a third hinge is added and the door and portion of door panel are protected by diamond-plate kick panels covering the bottom 32" on interior and exterior. Show number and size of super doors.
____________________
(Check following options as desired.)
B. ____ Observation Window in Entrance Door (a 14-1/2" x 24" heated observation window shall be provided in the entrance door It consists of three panes of glass with sealed air spaces between them. The window shall be supplied with heated glass and frame and unit shall be removable for replacement.)
C. ____ Mortise Lock - Heavy-duty, dead-bolt lock with full safety release capabilities. Mortise lock installations shall also be provided with stainless steel pins engaging the door frame on the hinged side.
D. ____ Strip Curtain - Sturdy, NSF-approved, clear-vinyl strip curtains shall permit easy passage while minimizing air infiltration.
11. Options - check as desired
A. ____Pressure Relief Port
(required for all freezers)
B. ____ Partition Walls - Insulated, 4"-thick metal-clad panels shall be provided to form separate compartments within the walk-in. A non-conductor strip must be built into all exterior panels at the joints where partitions butt to prevent transfer of heat from one compartment to another. Partition panels shall be Speed-Lok'ed to these panels. Construction shall be as specified in 7 above.
C. Roof Options - One of the following types must be used for any outdoor installation:
_____ Sectional prefab metal roof shall be used with structures installed outdoors on buildings of any length but not exceeding 34'7" in width. Roofs shall be made of stucco-embossed aluminum.
_____ Single-piece, pre-sized membrane roof system; maximum dimensions: 34'7" x 34'7".
_____ Built-up type by others.
Alarm Systems
_____ Audio-Visual Alarm System
_____ Audio-Visual Alarm with digital temperature readout Hi set point only
_____ Audio-Visual Alarm with digital temperature readout Hi Low set point with dry contact
E. _____ Double-swing Cart Door
F. Reach-in Doors for Product Loading (insulated solid type)
Insert correct sizes: 18-1/2" x 30" or 30" x 30"
Single _____ Size__________
Double _____ Size __________
G. Glass Display Doors
Number _____ Size __________
H. Wire Shelving
Cantilevered _____ Freestanding _____
No. of tiers _____ Finish _____
Width _____
Other Options
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
Mechanical Refrigeration
_____ Hermetic
_____ Semi-hermetic
_____ Self-contained
_____ Pre-assembled remote
_____ Condensing unit:
_____ Indoors (or) _____ Outdoors
Horsepower ______
Voltage __________
Phase ___________
Cycles __________
Low-ambient kit (winter controls) _________
(For multi-compartment units, provide plan view with compartment temperatures.)
13. Warranties
Bally shall warrant that any part of the structure it supplies (except the
refrigeration system and its related accessories) is free from defects in
materials or workmanship under normal use and service. The insulated panel
portion of the structure is warranted free from defects under normal use and
service for a period of 10 years from date of installation (but in no event
shall the warranty be in force for more than 10 years and 6 months from the date
the product was first shipped by Bally). Panel surface condition is warranted
free from defects under normal use and service for one year from installation,
provided the panel is stored and installed according to Bally's instructions.
Mechanical (including hardware, gasketing, Speed-lok assemblies, aluminum
weather roofs) and electrical components, except refrigeration systems (which
are covered by a separate warranty) are warranted to be free from defects under
normal use and service for one year from date of installation. (In no case shall
this portion of the warranty be in force for more than one year and six months
from the date the product was first shipped by Bally.) The warranty shall not
include any labor charges for replacement or repair of defective parts or
refrigeration. Full warranty information is to be provided with the walk-in.