PERFORMANCE REQUIREMENTS:
FIRE:
Meets special requirements of model building codes and is certified
and approved by the following authorities.
ULI - Underwriters Laboratories Inc.
FM - Factory Mutual
WH - Warnock Hersey
ULC - Underwriters Laboratories Canada NYFC -
New York State Toxicity Standard FM-4880 - Passed testing
for Class 1 Fire rating
ASTM-E84 - Flame Spread 17; smoke developed: 97 Finished
Panel
ULC S102 - Flame Spread 22; smoke developed: 67 Finished
Panel
ULC S101 - Passed Fire Endurance Tests without fastening
joint seams
UBC 17-6 - Passed Multi-story test with standard panels
THERMAL
TRANSMISSION:
ASTM C-518
ASTM C-236
VAPOR BARRIER:
ASTM E283 Air inflation “O” at 20 PSI
ASTM E331 Water penetration “O” at 20
PSI
STRUCTURAL:
ASTM E72
Vacuum chamber tested for wind and suction load deflections
on wall assemblies.
ASTM E72-9
The panel achieved a vertical load bearing capacity on standard
width to maximum 19,800 lbs. compressive force at .06" deflection.
Fatigue
Test:
Standard panels were tested by independent Laboratories for
long term deflection failure. The panels exceeded 2 million
alternate cycles without failure or damage.
BOND
STRENGTH:
The panel
was tested for Tensile Bond strength of the metal to foam interface
to more than 1200 lb. force without delamination.