Air-Cooled Condensers
for Refrigeration & Air Conditioning Systems |
|
BVC
- DIRECT DRIVE AIR COOLED CONDENSERS
For New or Replacement Needs
The BVC air-cooled condenser is
available in sizes ranging from 11 to 206 nominal tons THR. Constructed of heavy
gauge galvanized steel, the cabinet features zinc plated huck bolt assembly,
individually baffled fan sections, clean out panels, heavy gauge galvanized
steel motor mounts and quiet 850 RPM low speed fan motors.
Construction features include 3/8" O.D. copper tube (on models up to 183" in
length) or 1/2" O.D. copper tube (on models 243" in length and longer)
mechanically expanded on to aluminum fins, and THERMOSPAN™ coil design which
effectively eliminates tube failure on tube sheets.
Single fan width models (up to 6 fans long) and double fan width models (total
12 fan models) are available with 1 Hp 850 RPM (standard) or optional 1/2 Hp 550
/ 2 Hp 1140 RPM motors. A wide variety of fan cycling control and tube
circuiting options are offered to suit all specification requirements.
|
|
|
850 RPM quiet, low
speed fan motors
(optional 550 or 1140 RPM)
|
Rugged heavy gauge
galvanized steel rail motor mounts/support |
THERMOSPAN™ coil
design
|
• Complete selection of electrical fan cycling
and speed control options
• R134a, R22, R404a, R507
• 208-230/1/60, 208-230/3/60, 380/3/60, 460/3/60, 575/3/60, 200-220/3/50 and
380/3/50
• Optional fin materials and spacing available
SINGLE
ROW MODELS - 850 RPM
MODEL
NUMBER
BVC |
FAN
ROWS
|
MBH
CAPACITY THR @ 25°F TD, 12 FPI
R22/R404A
|
CFM
|
PIPING
CONNECTIONS ‡
|
DIMENSIONS In. (mm)
|
APPROX SHIPPING WEIGHT
Lbs.
(kg)
|
INLET
(OD)
|
OUTLET
(OD)
|
HEIGHT
|
WIDTH
|
LENGTH
|
BVC011 |
1 x 1
|
130.5
|
7470
|
1 3/8
|
1 1/8
|
48
1/2 (1232)
|
45
1/8 (1146)
|
49
1/2 (1257)
|
380
(173)
|
BVC012 |
1 x 1
|
146.8
|
7200
|
1 3/8
|
1 1/8
|
48
1/2 (1232)
|
45
1/8 (1146)
|
49
1/2 (1257)
|
410
(186)
|
BVC013 |
1 x 1
|
161.5
|
6930
|
1 5/8
|
1 1/8
|
48
1/2 (1232)
|
45
1/8 (1146)
|
49
1/2 (1257)
|
440
(200)
|
BVC014 † |
1 x 1
|
170.5
|
8840
|
1 5/8
|
1 1/8
|
48
1/2 (1232)
|
45
1/8 (1146)
|
62
1/2 (1588)
|
460
(209)
|
BVC016 † |
1 x 1
|
191.8
|
8590
|
1 5/8
|
1 1/8
|
48
1/2 (1232)
|
45
1/8 (1146)
|
62
1/2 (1588)
|
510
(232)
|
BVC022 |
1 x 2
|
261.0
|
14900
|
2 1/8
|
1 3/8
|
48
1/2 (1232)
|
45
1/8 (1146)
|
96
1/2 (2451)
|
620
(282)
|
BVC024 |
1 x 2
|
289.5
|
14400
|
2 1/8
|
1 3/8
|
48
1/2 (1232)
|
45
1/8 (1146)
|
96
1/2 (2451)
|
690
(314)
|
BVC027 |
1 x 2
|
323.0
|
13900
|
2 1/8
|
1 3/8
|
48
1/2 (1232)
|
45
1/8 (1146)
|
96
1/2 (2451)
|
750
(341)
|
BVC032 † |
1 x 2
|
383.5
|
17200
|
2 1/8
|
1 5/8
|
48
1/2 (1232)
|
45
1/8 (1146)
|
122
1/2 (3112)
|
890
(405)
|
BVC037 |
1 x 3
|
440.0
|
21600
|
2 5/8
|
1 5/8
|
48
1/2 (1232)
|
45
1/8 (1146)
|
143
1/2 (3645)
|
970
(441)
|
BVC041 |
1 x 3
|
484.3
|
20800
|
2 5/8
|
1 5/8
|
48
1/2 (1232)
|
45
1/8 (1146)
|
143
1/2 (3645)
|
1070
(486)
|
BVC043 † |
1 x 3
|
516.3
|
26500
|
2 5/8
|
1 5/8
|
48
1/2 (1232)
|
45
1/8 (1146)
|
182
1/2 (4636)
|
1170
(532)
|
BVC048 † |
1 x 3
|
570.0
|
25800
|
2 5/8
|
1 5/8
|
48
1/2 (1232)
|
45
1/8 (1146)
|
182
1/2 (4636)
|
1310
(595)
|
BVC056 |
1 x 4
|
673.5
|
35900
|
2 5/8
|
2 1/8
|
48
1/2 (1232)
|
45
1/8 (1146)
|
242
1/2 (6160)
|
1650
(750)
|
BVC063 |
1 x 4
|
757.0
|
35200
|
2 5/8
|
2 1/8
|
48
1/2 (1232)
|
45
1/8 (1146)
|
242
1/2 (6160)
|
1810
(823)
|
BVC068 |
1 x 4
|
825.0
|
34300
|
2 5/8
|
2 1/8
|
48
1/2 (1232)
|
45
1/8 (1146)
|
242
1/2 (6160)
|
1990
(905)
|
BVC079 |
1 x 5
|
946.4
|
44100
|
2 5/8
|
2 1/8
|
48
1/2 (1232)
|
45
1/8 (1146)
|
302
1/2 (7684)
|
2300
(936)
|
BVC085 |
1 x 5
|
1031.0
|
42900
|
2 5/8
|
2 5/8
|
48
1/2 (1232)
|
45
1/8 (1146)
|
302
1/2 (7684)
|
2530
(1150)
|
BVC095 |
1 x 6
|
1136.0
|
52900
|
3 1/8
|
3 1/8
|
48
1/2 (1232)
|
45
1/8 (1146)
|
362
1/2 (9208)
|
2880
(1309)
|
BVC103 |
1 x 6
|
1237.0
|
51500
|
3 1/8
|
3 1/8
|
48
1/2 (1232)
|
45
1/8 (1146)
|
362
1/2 (9208)
|
3150
(1432)
|
†
Derate capacity by 8% and air flow by 12% on these models when
operating on 208-230/1/60
‡ Applicable for 16°F to 30°F design TD
DOUBLE
ROW MODELS - 850 RPM
MODEL
NUMBER
BVC |
FAN
ROWS
|
MBH
CAPACITY THR @ 25°F TD, 12 FPI
R22/R404A
|
CFM
|
PIPING CONNECTIONS ‡
|
DIMENSIONS In. (mm)
|
APPROX
SHIPPING
WEIGHT
Lbs.
(kg)
|
INLET
(OD)
|
OUTLET
(OD)
|
HEIGHT
|
WIDTH
|
LENGTH
|
BVC044 |
2 x 2
|
522.0
|
29900
|
2 1/8
|
1 3/8
|
48
1/2 (1232)
|
87
5/8 (2226)
|
96
1/2 (2451)
|
1070
(486)
|
BVC049 |
2 x 2
|
587.5
|
28800
|
2 1/8
|
1 3/8
|
48
1/2 (1232)
|
87
5/8 (2226)
|
96
1/2 (2451)
|
1200
(545)
|
BVC054 |
2 x 2
|
646.0
|
27700
|
2 1/8
|
1 3/8
|
48
1/2 (1232)
|
87
5/8 (2226)
|
96
1/2 (2451)
|
1330
(605)
|
BVC057 † |
2 x 2
|
688.3
|
35300
|
2 1/8
|
1 5/8
|
48
1/2 (1232)
|
87
5/8 (2226)
|
122
1/2 (3112)
|
1400
(636)
|
BVC064 † |
2 x 2
|
767.0
|
34300
|
2 1/8
|
1 5/8
|
48
1/2 (1232)
|
87
5/8 (2226)
|
122
1/2 (3112)
|
1590
(723)
|
BVC073 |
2 x 3
|
881.3
|
43200
|
2 5/8
|
1 5/8
|
48
1/2 (1232)
|
87
5/8 (2226)
|
143
1/2 (3645
|
1720
(782)
|
BVC081 |
2 x 3
|
969.0
|
41600
|
2 5/8
|
1 5/8
|
48
1/2 (1232)
|
87
5/8 (2226)
|
143
1/2 (3645
|
1920
(873)
|
BVC086 † |
2 x 3
|
1032.0
|
53000
|
2 5/8
|
1 5/8
|
48
1/2 (1232)
|
87
5/8 (2226)
|
182
1/2 (4636)
|
2060
(936)
|
BVC096 † |
2 x 3
|
1151.0
|
51500
|
2 5/8
|
1 5/8
|
48
1/2 (1232)
|
87
5/8 (2226)
|
182
1/2 (4636)
|
2340
(1064)
|
BVC112 |
2 x 4
|
1347.0
|
71800
|
2 5/8
|
2 1/8
|
48
1/2 (1232)
|
87
5/8 (2226)
|
242
1/2 (6160)
|
2780
(1264)
|
BVC126 |
2 x 4
|
1514.0
|
70500
|
2 5/8
|
2 1/8
|
48
1/2 (1232)
|
87
5/8 (2226)
|
242
1/2 (6160)
|
3100
(1409)
|
BVC137 |
2 x 4
|
1650.0
|
68600
|
2 5/8
|
2 1/8
|
48
1/2 (1232)
|
87
5/8 (2226)
|
242
1/2 (6160)
|
3460
(1573)
|
BVC158 |
2 x 5
|
1893.0
|
88100
|
2 5/8
|
2 1/8
|
48
1/2 (1232)
|
87
5/8 (2226)
|
302
1/2 (7684)
|
4000
(1818)
|
BVC172 |
2 x 5
|
2062.0
|
85800
|
2 5/8
|
2 5/8
|
48
1/2 (1232)
|
87
5/8 (2226)
|
302
1/2 (7684)
|
4460
(2027)
|
BVC190 |
2 x 6
|
2271.0
|
106000
|
3 1/8
|
3 1/8
|
48
1/2 (1232)
|
87
5/8 (2226)
|
362
1/2 (9208)
|
4850
(2205)
|
BVC206 |
2 x 6
|
2475.0
|
103000
|
3 1/8
|
3 1/8
|
48
1/2 (1232)
|
87
5/8 (2226)
|
362
1/2 (9208)
|
5400
(2455)
|
†
Derate capacity by 8% and air flow by 12% on these models when
operating on 208-230/1/60
‡ Applicable for 16°F to 30°F design TD
ELECTRICAL DATA - 850 RPM MODELS 60Hz
NO.
OF
FANS
|
208-230/1/60 *
|
208-230/3/60
|
460/3/60
|
575/3/60
|
TOTAL
FLA
|
MCA
|
TOTAL
FLA
|
MCA
|
TOTAL
FLA
|
MCA
|
TOTAL
FLA
|
MCA
|
1
|
3.4
|
4.3
|
5.9
|
7.4
|
2.9
|
3.6
|
2.3
|
2.9
|
2
|
6.8
|
7.7
|
11.8
|
13.3
|
5.8
|
6.5
|
4.6
|
5.2
|
3
|
10.2
|
11.1
|
17.7
|
19.2
|
8.7
|
9.4
|
6.9
|
7.5
|
4
|
13.6
|
14.5
|
23.6
|
25.1
|
11.6
|
12.3
|
9.2
|
9.8
|
5
|
NA
|
NA
|
29.5
|
35.1
|
14.5
|
15.2
|
11.5
|
12.1
|
6
|
20.4
|
21.3
|
35.4
|
40.1
|
17.4
|
20.1
|
13.8
|
15.1
|
8
|
NA
|
NA
|
47.2
|
50.1
|
23.2
|
25.1
|
18.4
|
20.1
|
10
|
NA
|
NA
|
59.0
|
70.1
|
29.0
|
30.1
|
23.0
|
25.1
|
12
|
NA
|
NA
|
70.8
|
80.1
|
34.8
|
40.1
|
27.6
|
30.0
|
*Not available on 4 fan, 5
fan single row models and 6 fan models 182 1/2" and longer.
|
For 50Hz capacities, please contact
BMIL International, Inc.
Copyright 2009, BMIL Technologies, LLC., Inc. All rights reserved
4915 Arendell St., #313, Morehead City, NC 28557, 252-727-0994
Names and Logos are registered Trademarks of their respective companies.
Send comments on this web site to bmil@bmil.com.
Last revised:
November 20, 2011
|